Model NO.: YJV
Material Shape: Round Wire
Certification: ISO9001, CE, UL, CCC, RoHS, VDE
Brand: Ronda
Colour: Customized
Application Standard: IEC60227, IEC60592, IEC60228, IEC60331
Core: Annealed Copper
Trademark: Ronda
Transport Package: Export Package
Specification: Low Voltage
Origin: Shanghai China
HS Code: 8544601200
Model NO.: YJV
Material Shape: Round Wire
Certification: ISO9001, CE, UL, CCC, RoHS, VDE
Brand: Ronda
Colour: Customized
Application Standard: IEC60227, IEC60592, IEC60228, IEC60331
Core: Annealed Copper
Trademark: Ronda
Transport Package: Export Package
Specification: Low Voltage
Origin: Shanghai China
HS Code: 8544601200
Steve Wei  Sales ManagerUnderground XLPE Insulated Copper Power Wire Cable
1.Application
This cable is used as power distribution and transmission line at rated voltage 0.6/1KV which can be fixed installed.
Â
2.Service Characteristics
1.The long time working temperature of the conductor should not be higher than 90 ºC
2.When conductor is in short-circuit (max. 5s), the conductor temperature should not higher than 250ºC.
3.While installation the ambient temperature should not be lower than 0 ºC and the bending radius should not be less than 10 times of outer diameter of cable.
Available model upon request as below.
Â
            Products Name | Model |
Copper Core XLPE Insulated PVC Sheathed Electric Cable   (Cu/XLPE/PVC) Aluminum Core XLPE Insulated PVC Sheathed Electric Cable  (Al/XLPE/PVC) |
YJV YJLV |
Copper Core XLPE Insulated Steep Tape Armoured PVC Sheathed Electric Cable  (Cu/XLPE/PVC/STA/PVC) Aluminum Core XLPE Insulated Steep Tape Armoured PVC Sheathed Electric Cable (Al/XLPE/PVC/STA/PVC) |
YJV22 YJLV22 |
Copper Core XLPE Insulated Steep Wire Armoured PVC Sheathed Electric Cable  (Cu/XLPE/PVC/SWA/PVC) Aluminum Core XLPE Insulated Steep Wire Armoured PVC Sheathed Electric Cable (Al/XLPE/PVC/SWA/PVC) |
YJV32,42 YJLV32,42 |
Note: Low smoke Zore Halogen, Flame Retardant, copper screened type are also available upon request.
3.Technology Property
3.1 Bending Radius
Single Core Cable Permitted Bending Radius=20 (d+D)±5%
Multi Cores Cable Permitted Bending Radius=15 (d+D)±5%
D=Outer Diameter Of Cable (mm)
d=Outer Diameter Of Conductor (mm)
Â
3.2 Installation Temperature
Preheat is required when temperature is lower than 0ºC
Â
3.3 Installation Drop
Cable Installation is not limited by level drop.
4.Other Available Power Cables 1-30KV
>>Power and signal cable 0,6/1 kV, PVC insulated and sheathed
>>Power and signalling cable 0,6/1 kV, PVC insulated and sheathed, with concentric protective Cu conductor
>>Power cable 0,6/1 kV, PVC insulated and sheathed with corrugated concentric protective Cu conductor
>>Power and signalling cable 0,6/1 kV, PVC insulated and sheathed, with steel tapes armour
>>Power and signal cable 0,6/1 kV, PVC insulated and sheathed, with armour of round galvanized steel wires
>>Power and signal cable 0,6/1 kV XLPE insulated, PVC sheathed
>>Power and signal cable 0,6/1 kV, XLPE insulated, PVC sheathed, with concentric protective Cu conductor
>>Power and signal flexible cable 0,6/1 kV, insulated with rigid EPM-rubber, PVC sheathed, with reduced release of corrosive gases
>>Power cable 0,6/1 kV, PVC insulated and sheathed, with Al conductors
>>Power cable 0,6/1 kV, PVC insulated and sheathed, with Al conductors and concentric protective corrugated Cu conductorÂ
>>Medium voltage single core cable 6/10 kV, 12/20 kV, 18/30 kV, XLPE insulated, PVC sheathed, with screen of Cu conductors
>>Medium voltage single core cable 6/10 kV, 12/20 kV, 18/30 kV, XLPE insulated, PE sheathed, with screen of Cu conductorsÂ
>>Medium voltage single core cable 6/10 kV, 12/20 kV, 18/30 kV, XLPE insulated, PE sheathed, with screen of Cu conductors, longitudinally watertight
>>Medium voltage single core cable 6/10 kV, 12/20 kV, 18/30 kV, XLPE insulated, PVC sheathed, with Al conductors and screen of Cu conductors
>>Medium voltage single core cable 6/10 kV, 12/20 kV, 18/30 kV, XLPE insulated, PE sheath, with Al conductors and screen of Cu conductors
>>Medium voltage single core cable 6/10 kV, 12/20 kV, 18/30 kV, XLPE insulated, PE sheathed, with Al conductors and screen of Cu conductors, longitudinally watertight
>>Medium voltage multi core cable 6/10 kV, XLPE insulated, PVC sheathed, with screens of Cu conductors

5.Self-supporting Cable Bundles ( Aerial Insulated Cables)
>>Self-supporting cable bundle 0,6/1 kV with XLPE-insulation

6.Halogen Free Cables And Wires
>>Halogen-free fine wired conductor, with improved properties under fireÂ
>>Single core flexible cable, suited for photovoltaic and solar systems, up to 1,8kV, special HEPR insulated
>>Halogen-free installation cable 300/500 V, with improved properties under fire
>>Halogen-free signal cable, with improved properties under fire
>>Halogen-free signal cable with concentric protective Cu conductor, with improved properties under fireÂ
>>Halogen-free power and signal cable 0,6/1 kV , with improved properties under fire
>>Halogen-free power and signal cable 0,6/1 kV, with concentric protective Cu conductor, with improved properties under fire
>>Halogen-free power and signal cable 0,6/1 kV, with improved properties under fire, and 30-minute circuit integrity maintenance
>>Halogen-free power and signal cable 0,6/1 kV, with improved properties under fire, and 90-minute circuit integrity maintenance
>>Halogen-free power and signal cable 0,6/1 kV, with concentric protective Cu conductor, with improved properties under fire, and 30-minute circuit integrity maintenance
>>Halogen-free power and signal cable 0,6/1 kV, with concentric protective Cu conductor, with improved properties under fire, and 90-minute circuit integrity maintenance
>>Flexible halogen-free power cable 0,6/1 kV, with improved properties under fire, and 90-minute retained electric functionalityÂ

For more information
Steve Wei  Sales Manager
TEL: 0086 183 1708 9408
 Steve Wei  Sales Manager
Underground XLPE Insulated Copper Power Wire Cable
1.Application
This cable is used as power distribution and transmission line at rated voltage 0.6/1KV which can be fixed installed.
Â
2.Service Characteristics
1.The long time working temperature of the conductor should not be higher than 90 ºC
2.When conductor is in short-circuit (max. 5s), the conductor temperature should not higher than 250ºC.
3.While installation the ambient temperature should not be lower than 0 ºC and the bending radius should not be less than 10 times of outer diameter of cable.
Available model upon request as below.
Â
            Products Name | Model |
Copper Core XLPE Insulated PVC Sheathed Electric Cable   (Cu/XLPE/PVC) Aluminum Core XLPE Insulated PVC Sheathed Electric Cable  (Al/XLPE/PVC) |
YJV YJLV |
Copper Core XLPE Insulated Steep Tape Armoured PVC Sheathed Electric Cable  (Cu/XLPE/PVC/STA/PVC) Aluminum Core XLPE Insulated Steep Tape Armoured PVC Sheathed Electric Cable (Al/XLPE/PVC/STA/PVC) |
YJV22 YJLV22 |
Copper Core XLPE Insulated Steep Wire Armoured PVC Sheathed Electric Cable  (Cu/XLPE/PVC/SWA/PVC) Aluminum Core XLPE Insulated Steep Wire Armoured PVC Sheathed Electric Cable (Al/XLPE/PVC/SWA/PVC) |
YJV32,42 YJLV32,42 |
Note: Low smoke Zore Halogen, Flame Retardant, copper screened type are also available upon request.
3.Technology Property
3.1 Bending Radius
Single Core Cable Permitted Bending Radius=20 (d+D)±5%
Multi Cores Cable Permitted Bending Radius=15 (d+D)±5%
D=Outer Diameter Of Cable (mm)
d=Outer Diameter Of Conductor (mm)
Â
3.2 Installation Temperature
Preheat is required when temperature is lower than 0ºC
Â
3.3 Installation Drop
Cable Installation is not limited by level drop.
4.Other Available Power Cables 1-30KV
>>Power and signal cable 0,6/1 kV, PVC insulated and sheathed
>>Power and signalling cable 0,6/1 kV, PVC insulated and sheathed, with concentric protective Cu conductor
>>Power cable 0,6/1 kV, PVC insulated and sheathed with corrugated concentric protective Cu conductor
>>Power and signalling cable 0,6/1 kV, PVC insulated and sheathed, with steel tapes armour
>>Power and signal cable 0,6/1 kV, PVC insulated and sheathed, with armour of round galvanized steel wires
>>Power and signal cable 0,6/1 kV XLPE insulated, PVC sheathed
>>Power and signal cable 0,6/1 kV, XLPE insulated, PVC sheathed, with concentric protective Cu conductor
>>Power and signal flexible cable 0,6/1 kV, insulated with rigid EPM-rubber, PVC sheathed, with reduced release of corrosive gases
>>Power cable 0,6/1 kV, PVC insulated and sheathed, with Al conductors
>>Power cable 0,6/1 kV, PVC insulated and sheathed, with Al conductors and concentric protective corrugated Cu conductorÂ
>>Medium voltage single core cable 6/10 kV, 12/20 kV, 18/30 kV, XLPE insulated, PVC sheathed, with screen of Cu conductors
>>Medium voltage single core cable 6/10 kV, 12/20 kV, 18/30 kV, XLPE insulated, PE sheathed, with screen of Cu conductorsÂ
>>Medium voltage single core cable 6/10 kV, 12/20 kV, 18/30 kV, XLPE insulated, PE sheathed, with screen of Cu conductors, longitudinally watertight
>>Medium voltage single core cable 6/10 kV, 12/20 kV, 18/30 kV, XLPE insulated, PVC sheathed, with Al conductors and screen of Cu conductors
>>Medium voltage single core cable 6/10 kV, 12/20 kV, 18/30 kV, XLPE insulated, PE sheath, with Al conductors and screen of Cu conductors
>>Medium voltage single core cable 6/10 kV, 12/20 kV, 18/30 kV, XLPE insulated, PE sheathed, with Al conductors and screen of Cu conductors, longitudinally watertight
>>Medium voltage multi core cable 6/10 kV, XLPE insulated, PVC sheathed, with screens of Cu conductors

5.Self-supporting Cable Bundles ( Aerial Insulated Cables)
>>Self-supporting cable bundle 0,6/1 kV with XLPE-insulation

6.Halogen Free Cables And Wires
>>Halogen-free fine wired conductor, with improved properties under fireÂ
>>Single core flexible cable, suited for photovoltaic and solar systems, up to 1,8kV, special HEPR insulated
>>Halogen-free installation cable 300/500 V, with improved properties under fire
>>Halogen-free signal cable, with improved properties under fire
>>Halogen-free signal cable with concentric protective Cu conductor, with improved properties under fireÂ
>>Halogen-free power and signal cable 0,6/1 kV , with improved properties under fire
>>Halogen-free power and signal cable 0,6/1 kV, with concentric protective Cu conductor, with improved properties under fire
>>Halogen-free power and signal cable 0,6/1 kV, with improved properties under fire, and 30-minute circuit integrity maintenance
>>Halogen-free power and signal cable 0,6/1 kV, with improved properties under fire, and 90-minute circuit integrity maintenance
>>Halogen-free power and signal cable 0,6/1 kV, with concentric protective Cu conductor, with improved properties under fire, and 30-minute circuit integrity maintenance
>>Halogen-free power and signal cable 0,6/1 kV, with concentric protective Cu conductor, with improved properties under fire, and 90-minute circuit integrity maintenance
>>Flexible halogen-free power cable 0,6/1 kV, with improved properties under fire, and 90-minute retained electric functionalityÂ